I just made an album for you guys of one of our shelf/rack hybrid pods.
http://imgur.com/a/OgAHz
East side of our Gamma pod. The rack on the far right currently draws 70.5 kW, mostly SP35s. We used to have 73.5 kW in there, but one SP30 customer asked to have their machine shipped out.
The "Pull wire" thing is what we use as a door for access to the hot aisle.
These photos were taken at the Toomim Brothers Bitcoin Mining Concern facility in central Washington. You can visit
http://toom.im for more information.

East side of Gamma. Thermal photo using a Seek Thermal camera. The camera is miscalibrated, subtract 5°C from all the numbers to get the accurate values. Ambient temperature was about 18°C inside the datacenter when this photo was taken.
Sorry for the rotated image. My pone has its USB port on the side, and Seek's software doesn't like that. Too lazy to fix it in post-production. Rotate clockwise 90° to correspond to the previous image.

We just finished up this section yesterday. Currently only 12 Antminer S5s in there, but we'll be adding about 35 more soon. Since S5s have a low delta T (about 5°C), we've found that we can put two S5s front-to-back while still keeping the intake temperature for the rear S5 well within limits. Thus, this is a 2x2x3 grid.

The plastic we put up for hot air containment is apparently partially transparent to infrared light. Kinda neat. The solid white panels, on the other hand, are not.
Rotate clockwise 90° to correspond to the previous image.