I'm trying to build ducting to get heat from 4 s7s out of the basement through the exhaust for the dryer and want to know if it's big enough or needs to be widened? Should the exhaust have it's own fans pulling air?

1 watt = about 3.4 btu

so 1000 watts = 3400 btu

200 watts = 680 btu

thus  the s-7 is close to a 4000btu heater

the cfm is about 200 at 4000 rpm fan speed