Great info, thanks !
I'm defintly getting a warehouse. Its much much bigger than i need but will have room to expand. It comes with 460amp 3-phase power so i should be good to go.
Last niggle points: The 3-phase is 208/240VAC right? Odds are it is. Then remains the phase power setup: Is it Delta w/Wild leg or is it true 3-phase Wye (star)? Ref
https://en.wikipedia.org/wiki/High-leg_deltaIf it is 480V (which WILL be Wye format) can still be used but breakers will be setup differently because instead of getting power from leg-to-leg (phases) which is the full 480V you would need power from each leg to neutral to get
240V 277VAC.