I was just doing some research on the same subject earlier today. I stumbled across this and it looked promising.

https://www.coolmygarage.com/shop/gf-14-garage-fan-attic-cooler/

 A 12,000 BTU window A/C unit is actually *2 tons* not 1 ton.


I have to correct you on this.. 12,000BTU/hr is equal to 1 Ton of Refrigeration or 1TR is also equal to 3.51kW of heat

Yeah I think you are correct.

For most of us ac is not the way to go.  Exhausting the hot air works as long as the outside temp is under 100f

If you mine in a really hot place injecting a llttle bit of ac. To the cold section of the-mining space can help