Hi Guys,

I have a weird question. I know this has been talked over the tread but it is little different. Here is my setup.

I have about 50 rigs in a warehouse. I am having excessive heat problem right now. Ambient temperature is ~90F in the room if I put all the rigs up.

There is a 5 ton Industrial type AC system at the top. Also, 1 exhaust motor on the wall which sucks the heated air.

I am not sure what solution I should go. I've talked HVAC guy and he suggested a load calculation for the room (2000SF). When I do math, it goes 12 ton AC unit required for this project.

I am wondering that adding exhaust fan makes any difference on top of the current setup? Please advise.


AC is a waste of electricity unless you have  free power, your exhuast fans need to be ABOVE your rigs not in at the same level and you  also need to make sure your room is somewhat presurerized

you can tell this by when you open the doors you feel the suction of the exhaust fans pulling heat up.

I have 30 rigs in my garage with only 1 of six exhasut fans going and my temps are like 30 degreees in winter, fall with three fans going like 60