I got 2 but planning to run only 1 in my apartment.
Well, I am planning to use the APW3++. It says that it wont provide more than 1200 W if ran from 110 V. My initial plan was to use one of the GFCI (
https://simple.m.wikipedia.org/wiki/GFCI) from the bathroom or kitchen since they have desicated 15 A breakers. But of APW3++ cant give the A3 more than 1200 W, theb I am SOL, right? That is when I started researching about using dryer plug.
Why do you think a sungle A3 should be fine to run from a 15A 120 V if the AWP3++ cant do well on 120 V?
If it will work, i will just use the GFCI
Keep in mind, electric in the USA is 120v, not 110v (1440W usable continuous on 15A).
I was running 2x vega 56s, 1x vega 64, and a L3+ overclocked (920W at the kill-a-watt using APW3++) on the same 15A 120v circuit. The breaker only tripped when my wife turned on the hair dryer.
Oh ya, My TV, laptop, and stereo amplifier are also on that circuit... So was the christmas tree over the holidays..
Well, but you only pulled 920 W for the APW3++, right? The Anitminer A3 needs 1400 W. Per the specifications page on the APW3++ it can only provide 1200 W on 110 V (but can supply 1600 W on 22 V). Like you said, if US is 120 V, then it can provide 1300 max? That is still less than what A3 needs (1400 W), right? Or am I missing something?