hello all
so I have had my Avalon 741 running in my garage for now and have an s9 on order.
I go the conduit in the ground and should have electricity run by this weekend.
My concern is the intake and exhaust, I have an existing shed about 10x10 with a window in the back. I'm going to put a shelf right in front of the window and use a fan to pull the air out.
I need help figuring out what fan to use. I have a large vorando fan that I can use in the mean time, but id like to get something more permanent that will fit in the window.
The other issue is intake. I'm going to need to cut wholes in the shed for intake. can you provide any insight on the best way to do this. I will post pictures of my shed after work.
If it were me and the shed is dedicated for miners I would do the following.
This kind of depends on size, but if it permits incorporate 2-4 large AC filters in one wall. Then on the opposite wall mount a couple of exhaust fans. I would go above the ~225 CFM output of the miners by 1.5-2x. So if you have 2 miners @ ~450CFM mount a 675-900 CFM exhaust fan(s). That should draw fresh clean air over the miners and the hot waste heat out. Obviously point the miner exhaust at the exhaust fans

As you add miners simply add or upgrade fans.