Can I run 2 A3's on a 10-30R 30A 125/250V outlet ?. We use this for dryers, but thought of using this to mine as this is the only 220v that I can find in my home ? However I understand this is old setup, will it work fine with continuous load. Thanks.  

I'm running 2 A3 and a L3+ on a 30A 240V circuit. Consumption is around 13A for all 3 devices. I could still do another 2 A3 and another L3+.



Awesome, Then I will go get an adapter Smiley. I also have a S9 and L3+, I will hook that up as well into this outlet. Thanks.

a 30A 240v circuit should be derated to 26A continuous load to be safe, so you have a total power draw of ~6.2kw on that circuit...thats good for like 4 A3's or 6 L3+

I'm at 12A with 2 A3 (undeclocked), 1 L3+ (overclocked) and a D-Link switch. I'm expecting to be able to do 4 A3 and 2 L3+ right at 24A (80% continuous).