https://imgur.com/eejULPGHey peeps, can anybody identify what kind of PDUs are used in this farm?
Also, I'm buying 30 AMP pdu's for my farm, link below. I've calculated I can only run 3x antminer S9's on this (230V input power), if I try to run 4 I think i'll trip the internal PDU breaker (set at 24 amps). Am I right? I'd like to get 4 Antminers / PDU if possible, any ideas based on my 230V input?
Link to the PDU's i'm specing:
https://www.cyberpowersystems.com/product/pdu/pdu30bhvt8r/ I don't have an answer to the PDU in the pic. But the PDU you spec'd is 24A total (recommended) and has 2x 16A breakers. So each 4 outlets is on a 16A breaker. You could run 4 off that PDU, **but** safe recommended 24x7 operation is 80% of the circuit. 30A * .80= 24 amps.
Look further down in this forum I posted a PDU thread with some recommendations.