Re: Harmonics in electrical system from mining off genset?
by
HoleShot
on 09/03/2018, 19:04:22 UTC
Yes, the 230V/133V is your 3-phase output.

You should connect your miners like this.

A,B legs to miner 1
B,C legs to miner 2
C,A legs to miner 3

Then continue to rotate like this until maximum power is reached. I would not use the neutral. I would not use the single phase output.