heh thanks for the link....may have to do that but still want to know if a 100amp panel with NO central a/c load on the house and only a clothes dryer and stove 30amp (I can make the dryer gas if I have to) ok to do or not
1) elec code wise running 2 of these beasts off a 100 amp panel code wise
2) I have to live there don't want to wake up tyring to an elec fire (or not)
anyway thanks if anyone off hand knows something on this (would not to sound like a complete idiot when/if I talk to an electrician on concerns)
Searing
If you can change the dryer and stove to gas, piece of cake. Each of the 2 220volt ckts will run 1 Neptune.
But if it's a fairly modern house it's also easy to upgrade. You just buy a 200 amp main breaker. You need to make sure the line coming into the main meter box from the pole, and the short trip from the meter box to the main breaker can handle it.
Check the gauge i.e. 0000?, then internet gauge/current charts.
200amp boxes are usually larger because of the average number of outlets, but if you have a few unused slots in you 100A you can use them for your miner circuits. If the existing box is full(or nearly), Then you can just add another 100A, 0r 50,etc sub panel. It's easy but electrician's fees add up quick. Best to buy an electrician friend lunch and maybe a BTC tip. Or YOU do the work and let them check it out.