I am in a 800sqft space with 20ft ceilings and a 3 ton HVAC unit that now seems to run 24/7.

Holy shit dude...you could be fighting like, 30,000watts with that unit. You just need an exhaust solution, not a 3 ton compressor.

Hum, no. 1 ton of cooling is 3517 Watt.  So a 3-ton HVAC can cool about 10.6kW of equipment, or a bit more assuming heat loss in the server room.

Some use no HVAC to cool 10.6kW of equipment, but that's a completely different DC cooling strategy Smiley