What's the total wattage on this?

I have 44.2 amps on 205v and 16.8 amps on 110v - That should be about 10,909 watts measured at the wall. There's probably some extra wattage for hubs, firewalls, pdu, etc. so call it 10KW.


Did you mean 44 amps at 208/240 and 89 amps at 115/120?  

I mean..

44 amps at 208V (44A x 208V = 9152W)
17 amps at 120V (17A x 120V = 2040W)

So, 11.1KW, minus 500W or so for other stuff.