Ok, that all makes sense, thanks for looking. Too bad I can't just use an adapter. I thought the plug configuration wouldn't matter because I was going from 4 prongs to 3 prongs anyway. Learning.

adapters add 1 more set of fail points.

remember you will be doing  3200 + 1700 = 4900 watts 24/7/365

or if you run the 2 s15 on low and 1 s19

950+950+3200 = 5100 watts

those are under rated limits but close so the less connections the better off you are.

And the pdu has multiple circuit breakers inside of it for safety sake.

I have like 14 of those pdus all used from ebay

as cheap as 35 and as much as 70 depends on how hot mining profit is.

I do like them. They have help prevent burn ups.



https://bitcointalk.org/index.php?topic=5334851.0


notice a guy set up a farm with adapters to sockets not pdus. look at last photo adapters to sockets