Okay, guys. Thanks everyone for the replies. I'm still having issues trying to figure this out. For circuit breaker panel I need to get one with 20 spaces for 20 outlets and 10 double pole breakers? Now since 17 series need two outlets, so each PS(cord) should have same amps for breakers?


Now the problem I'm having is understanding exactly what to buy and what amp breakers to use? Now i seen on one power supply spec for the t17+'s is 3600w and that is 16amps at 240v? SO, a 20amp breaker? Or do I use 25% rule 4700watt at 21amps, a 25amp breaker? Both cords from one miner should be on same breaker?

I see 220v and 240v interchanged a lot how does that factor in to my calculations, do i need to wait to power is hooked up to get accurate reading from meter to use in calculations?

And I know myself and i wont be able to resist OC them at some point. I already adhered to the fact that doing that will probably cause heatsink to come off, and if i want to fix myself it going to cost about $1000 in repair tools, time, frustration, etc. or pay to get them fixed.  already got a repair manual and watching videos.
 
Anyways, I have 2 t17+ and 2 s17+ atm...... Is there a way I can just have one or two outlets hooked up to a 220v pdu with a breaker for every outlet if they have that, just cut down on stuff till I do a make over when have all ten?