Post
Topic
Board Hardware
Re: S19 fan spec?
by
philipma1957
on 09/01/2022, 14:10:25 UTC
The specs I suggested would be if you are removing the original fans and replacing them with ducts and duct fan(s). If you are not removing the fans on the miner, then the specs are a lot lower since all you need to do is deliver the max airflow the miner will require and only overcome the static pressure of your ducts and filter.

The 10" AC infinity fan lists a static pressure spec of 1059 Pa, which is 108 mmH2O, so I'd guess it has a good chance of working if your ducts aren't too long.

as an aside that fan has a speed control which will allow you to reduce speed if needed.

Duct size reduction = less air flow  so maybe you can just run the fan at full speed.

if the ducts are 20 feet long you may need a booster fan near the exit at the window.