We will be converting mine to liquid cooling.
we are heat and spaced capped
we are looking at this company
I was never able to understand the economical logic behind using liquid cooling in mining, it's cool and all, but the cost is extremely high, if noise isn't an issue for you, why not just add more fans to the wall? or replace the ones you have with some strong fans like
this or
this I would like to hear more about why can't you improve your air cooling.?
in the first room which has lots of power it is a long rectangle
say 9 by 25ft
one long wall is not cutable.
one short wall has 9000 cfm input and the entrance door. no space to add input.
second long wall has 10000cfm input air.
the second short wall has 19000 cfm exit air
so 19k in and 19k out
the fans of the mining gear do 18900 cfm.
pretty balanced.
what can we do to do more air in we can add about 8800cfm of air
and more air out about 8800 cfm this is around 16 s19 at 3k watts each say 48 kwatts.
add the 100kwatt we are at we max at 148 kwatts.
we have over 225 kwatt to use so we waste 75 kwatts.
if we get 3 120kwatt max racks with liquid we can do 70-80 kwatts a unit gets us to 210-240 kwatts.