I am planning out a mining setup that has power coming in at 415Y/240V . This is located in Missouri USA.
I was looking for breaker panels for this setup, but I only see 480Y/277V three phase panels being sold around here an online.
The breaker panel will connect to 4x 100 Amp PDUs that will run 24x S19 each.
Anyone know where to find the right breaker panel for this setup?

Okay are you saying you have a 300kva three phase transformer?

You can not run 96  s19s.

3000 x 96 = 288,000 watts

Or 288 kwatts.

288/300 is greater than 80%

240/300 is 80%

240/3= 80 units tops not 96

I will tell you a trick a  600 volt not amp will handle 600 volts or less
A 480 volt not amp will handle 480 volts or less
A 240 volt not amp will handle 240 volts or less