Re: Cooling Question
by
psjw4450
on 13/05/2014, 11:55:33 UTC
I am currently using 40kw of electricity for my miners  and was wondering if a 2.5 ton AC would be sufficient to lower the ambient temperature between 80-90 F.  I have a 3000 cfm fan pulling air out of the room and a 3000 cfm fan bringing in 80 F air in.  The room temperature is 115 F.   Any suggestions would be helpful.  


some math 40kw is 40,000 x 4btu = 160,000 btu a 2.5 ton ac unit is 30,000 btu.

So my guess is no  it will not drop your temps from 115 to 90.

40kwatt is close to 100 s-1's

what miners do you own?

Mix of S1 and S2.  How many btus would be needed?