Anyone have a link for what mounting rails/ears? Or specs on what to buy?

Should add meant for Sp30.

The dimension allegedly are: D 554 X W 431 X H 88.4 mm.
I'm personally considering buying this: http://www.ebay.co.uk/itm/291075344625?ssPageName=STRK:MEWAX:IT&_trksid=p3984.m1423.l2649


Does anyone know if there will be any problem with plugging my 2 x SP30 at my apartment, in United Kingdom, to 230v 50Hz mains socket? Someone on the forum once mentioned something about some issue.

I just need the mounting ears for a standard data center 2U rack mount. Not sure what you call them. That seems like a ton of heat for an Apartment. I use air cooling in a Large Garage I pay for and its quite warm with 4000KW. Unless your Apartment is very Large?

I'm basically just curious, seems like a lot of power for an Apartment I guess.

4000KW would be a lot of heat, yes Wink 4000W isn't much at all if you can separate the heat from anywhere humans need to be (another bedroom). Heck you can cram 10KW into a single room if you've got two windows or split flow a single window. And remember in the UK for the majority of the year, our ambient is 2-10C so free AC from outside.

You'll have to split the physical sockets those SP30s are on but they'll run off a single 32A circuit fine. I wouldn't want anything else substantial on that circuit though. Fridge, microwave etc should be fine.

Most sensible flats will have 2x 32A circuits on a 63A RLD switch.