Most PDU manufactures max rating is 32amps.
Those miners are 1600w each.
9*1600 - 14.4kw per rack.
At 230volts thats 62.6amps per rack.
So 2x 32amp PDUs required....
Since that appears to be 3 phase power, each phase would have a draw of 3*1600=4800W/phase.
At 230 volts, that is 20.1 Amps per phase.
So something like
this 32 Amp PDU should work. (Don't know about price; probably not cheap.)
Correct, but the problem with the device you linked too is that you max out the "whole" PDUs urrent rating, Unless the whole device is rated at 32amps
per phase, and not the
whole device, which is highly unlikely, thus you need to split the devices plugged into two separate PDUs, as to not trip the devices over current protection.