If I order 20 SP30's for my 40U cabinet what size circuit will I need to power these machines, the sales guy at my data center is telling me I will need a 208V 30Amp 3 phase circuit.
Is this correct or is this guy out of his mind?
Thanks
Your going to need about 60KW of power for those, a hell of alot more than 1 208V 30A can give.