If I order 20 SP30's for my 40U cabinet what size circuit will I need to power these machines, the sales guy at my data center is telling me I will need a 208V 30Amp 3 phase circuit.
Is this correct or is this guy out of his mind?
Thanks
He's out of his mind. 208V 30A 3 phase is at most 20830sqrt(3)80% = 8 kW, which is enough to run two SP30s (or maybe three if you're willing to risk a breaker nuisance tripping on occasion).