Re: Anyone else blow a transformer? Whats a safe load?
by
chicagoleo
on 13/12/2014, 11:09:42 UTC
50Kva at 120v is 416amps..

so you have two hot legs.. your running 200amps so 100 on each leg as long as they are distributed evenly leaves you 3/4 load left over.(too the transformer). but if your sharing it with other houses thats not much.

The real question is what is your main breaker, and go buy a clamping amp meter, even your load over your two single phase legs and stay under 80% of your main breaker and you'll be fine.

Let me know if you need more info.

Thanks

Chicagoleo
========================