Re: Home Electricity supply
by
wh00per
on 16/12/2014, 03:55:44 UTC
1.4 kW will pull about 5.8 amps at  240v so you are safe to put 5 maybe 6 on your circuit. How many outlets are you sharing on the circuit? To add more you would need to upgrade the panel to 200A then you could add 2 more 40A RCD's. Also I would spread the amps over multiple outlets because the wiring in one outlet is probably not sufficient to handle 40A.

For example if I have an Antminer S4, which has a 1.4kW PSU, this is consuming 5.8amps? Therefore I can only have 40/5.8 = 6 S4's on this RCD?

Almost. You shouldn't run a circuit above 80% continuous. So keep your 40 amp circuit at 32 amps or less. 32/5.8 = 5x S4s.