Re: Cooling Question
by
psjw4450
on 13/05/2014, 12:45:14 UTC
I am currently using 40kw of electricity for my miners  and was wondering if a 2.5 ton AC would be sufficient to lower the ambient temperature between 80-90 F.  I have a 3000 cfm fan pulling air out of the room and a 3000 cfm fan bringing in 80 F air in.  The room temperature is 115 F.   Any suggestions would be helpful.  


some math 40kw is 40,000 x 4btu = 160,000 btu a 2.5 ton ac unit is 30,000 btu.

So my guess is no  it will not drop your temps from 115 to 90.

40kwatt is close to 100 s-1's

what miners do you own?

Mix of S1 and S2.  How many btus would be needed?  

I have to find my ac books as there is a formula.  Do you know the measurements of the room.

  Height  x Width  x Length   gives me cubic ft.  Also you have  80F temp for  intake of 3000cfm air.

Will that go to a higher number in the summer?



Thanks.  Room is 25x15 with 12 foot ceilings.  Summer it will probably reach 100 F outside so I would turn the intake around and push 6000 cfm of hot air out. No sense in bringing 100 F air in.